![]() |
|
|
|
|
![]() |
||||
|
IIS-350-U Application Notes These application notes are updated occassionally for quick reference. If you are unable to find information regarding your IIS application here, please contact our IOTA Technical Services Team. Maximum distance for operating a load Wiring for switchable fixtures in indoor HID applications Outdoor HID applications with photo switch or timer MAXIMUM DISTANCE FOR OPERATING A LOAD The distance at which the IIS Inverter will operate a load is determined by three things:Back to top WIRING FOR SWITCHABLE FIXTURES IN INDOOR HID APPLICATIONS Indoor HID fixtures on the emergency circuit MUST NOT be connected to a switch. Safety code requirements dictate that emergency lighting provide a specified level of illumination within 10 seconds. HID lamps cannot meet this specification, therefore any indoor HID lamps on the emergency circuit must not be switched off. If no HID lamps are being utilized on the emergency circuit, and a switch is present, then use the IIS-375-I for this application.Back to top OUTDOOR HID APPLICATIONS WITH PHOTO SWITCH OR TIMER Currently, there are no code requirements to light the exterior emergency lights of a building in daylight hours, therefore an automatic photo switch or timer may be present. If a timer is used, be sure that the timer motor is also connected to the IIS-350-U and that its load was included in the calculations. If power fails, and no emergency power is connected to the timer switch, the timer will not illuminate the connected lamps. Back to top | ||||||||||||||||||||||||||||||||||||||||||||||||||