IIS-125 Application Notes
These application notes are updated occassionally for quick reference. If you are unable to find information regarding your IIS application here, please contact our IOTA Technical Services Team.
Maximum distance for operating a load
MAXIMUM DISTANCE FOR OPERATING A LOAD
The distance at which the IIS Inverter will operate a load is determined by three things:
1) The wattage of the load
2) The voltage (120V or 277V)
3) The gauge of the wire
Below is a reference chart to help determine the distance (in feet) allowing for a 3% voltage drop.
| |
120V |
277V* |
| Watts |
14 gauge |
12 gauge |
10 gauge |
14 gauge |
| 50 watts |
1600 ft |
2468 ft |
4084 ft |
8623 ft |
| 100 watts |
809 ft |
1249 ft |
2066 ft |
4311 ft |
| 125 watts |
646 ft |
997 ft |
1649 ft |
3445 ft |
*Incandescent lamps are not generally operated above 140 volts except by special permission by the authority having jurisdiction.