The I-160 is designed to provide maximum light output in a power-failure situation. With a rated output of 3000 lumens, the I-160 is capable of keeping a single lamp operating at nearly 100% its original lumens. And since it features a
user replaceable battery, there's no need to ever replace the entire unit in case of battery failure. |
|
| LUMEN OUTPUT |
|
(1) Lamp - 3000 lumens (2) lamps - 1500 lumens per lamp |
| LAMPS OPERATED |
|
Most 2'-8' single, bipin T8 & T12, 2'-4' T5 HO or VHO linear, 42W 4-pin, and long compact fluorescent lamps |
| EMERGENCY OPERATION |
|
90 Minutes |
| PRODUCT DESCRIPTION |
| The I-160 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-160 switches to the emergency mode and operates one or two of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can and is provided with 2' of 3/8" flex for wiring to the fixture. The I-160 can be mounted next to or on top of the fixture, and is UL Listed for retrofit applications. The I-160 can be used with most 2'-8' lamps, with an initial output of up to 3000 lumens for one or two lamps, and features lamp selector leads for optimizing light output for designated lamp types. |
|
||||
| AVERAGE LUMEN RATINGS | ||
| Lamp | 1 Lamp | 2 Lamps |
| F40 T12/ES | 2700 | 2675 |
| F96 T12 | 2850 | |
| F25 T8 | 2300 | 2600 |
| F32 T8 | 3000 | 3000 |
| F96 T8 | 2950 | |
| 28W T5 | 2450 | |
| 54W HO T5 | 2700 | |
| 42W Compact | 2900 | 3000 |
| 57W Compact | 2700 | |
| 70W Compact | 2800 | |
| 40W Long Compact | 2600 | |
| 50W Long Compact | 2500 | |
| 55W Long Compact | 2500 | |
| 55W Circline T5 | 2700 | |
| FEATURES | |
|
U.L. and C.U.L. Listed Long-life high-temperature recyclable Ni-Cad battery Painted steel case 90-minute emergency operation Includes test switch/charge indicator accessory kit Dual voltage 120/277V, 60Hz 5-year warranty. See Warranty Page for details. Selectable lamp leads for optimizing light output for desired lamp type Remote Mounting Pan Option Meets or exceeds all National Electrical Code and Life Safety Code Emergency Lighting Requirements International Voltage and Damp Location Models Available |
|
| DIMENSIONS |
|