The I-232 is designed to operate two fluorescent lamps in parallel, insuring emergency light output from one lamp even if the other lamp is burnt out or otherwise inoperable. In the case of only one lamp operating, the I-232 will provide more power to the single lamp for additional lumen output.
LUMEN OUTPUT
(2) lamps - 1400 lumens (700 lumens per lamp)
LAMPS OPERATED
Most 2'-4' single, bipin T8 & T12, long compact, HO or VHO fluorescent lamps
EMERGENCY OPERATION
90 Minutes

PRODUCT DESCRIPTION
The I-232 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-232 switches to the emergency mode and operates two of the existing lamps in parallel for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can. The I-232 can be mounted in the wireway or on top of the fixture, and is UL Listed for retrofit applications. The I-232 can be used with most 2'-4' lamps, with an initial output of up to 1400 lumens for two lamps (700 lumens each lamp). The I-232 is compatible with all electronic or magnetic, series or parallel output, multi-lamp ballasts.



TECHNICAL SPECIFICATIONS
Input Voltage

Input Wattage

Lamps Operated



Emergency Operation

Initial Illumination


Approval

Weight

120/277V 60Hz

4 Watts

Most 2'-4' single, bipin
T8 & T12 HO or VHO
fluorescent lamps

90 Minutes

(2) lamps - 1400 lumens*
(700 lumens each lamp)

UL and CUL Listed

3.6 lbs

*Initial Illumination is 1000 lumens when one lamp is inoperable

AVERAGE LUMEN RATINGS
Lamp 2 Lamps
F17 T8 1000
F32 T8 1400
F20 T12 900
F40 T12 1200





FEATURES
U.L. and C.U.L. Listed

Long-life high-temperature recyclable Ni-Cad battery

Time Delay Enhancement

Open Circuit Isolation

Galvanized steel case

90-minute emergency operation

For use with any magnetic or electronic ballast

Includes test switch/charge indicator accessory kit

DL model suitable for use in enclosed and gasketed fixtures

Dual voltage 120/277V, 60Hz

5-year warranty. See Warranty Page for details.

Meets or exceeds all National Electrical Code and
Life Safety Code Emergency Lighting Requirements

Damp Location and International Voltage Models Available


DIMENSIONS