LUMEN OUTPUT
(1) Lamp - 1400 lumens
(2) lamps - 700 lumens per lamp
LAMPS OPERATED
Most 2'-8' single, bipin T8 & T12, long compact
and 2'-4' 14W to 54W T5 HO or VHO fluorescent lamps
EMERGENCY OPERATION
90 Minutes

PRODUCT DESCRIPTION
The I-320 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-320 switches to the emergency mode and operates one or two of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can, and can be mounted in the wireway or on top of the fixture. The I-320 can be used with most 2'-8' T8 thru T12 and 2'-4' 14W to 54W T5 lamps, with an initial output of up to 1400 lumens for one or two lamps and features lamp selector leads for optimizing light output for the designated lamp type. The I-320 delivers high performance in a slim design, and is ideal for use in fixtures where compartment space is limited.



TECHNICAL SPECIFICATIONS
Input Voltage

Input Wattage

Lamps Operated



Emergency Operation

Initial Illumination



Operating Temp

Approval

Weight

120/277V 60Hz

3.5 Watts

Most 2'-8' single, bipin T8 & T12,
long compact, or 2'-4' 14W to 54W T5
HO or VHO fluorescent lamps

90 Minutes

(1) Lamp 1400 lumens
(2) lamps 700 lumens each lamp
*Long compact - (1) lamp only

0 to 55 degrees C

UL and CUL Listed

2.5 lbs

AVERAGE LUMEN RATINGS
Lamp 1 Lamp 2 Lamps
F17 T8 1125 1100
F25 T8 1200 1150
F28 T8 1225
F32 T8 1350 1350
8' T8 (FO96) (59W) 1400
F20 T12 680
F40 T12 1150
F48 T12 1150
8' T12 (F96T12) (60W) 1125
14W T5 850
21W T5 1150
24W T5 925
28W T5 1050
39W T5 1100
54W T5 1150
20W Circline 1125
40W Circline 1125
57W PL CF Quad 4 Pin 1160
70W PL CF Quad 4 Pin 1200
36W Long Compact 1050
40W Long Compact 1050
50W Long Compact 1100
55W Long Compact 1100


FEATURES
U.L. and C.U.L. Listed

Will cold start and operate all specified lamps

Long-life high-temperature recyclable Ni-Cad battery

90-minute emergency operation

Dual voltage 120/277V, 60Hz

Time Delay Enhancement

Open Circuit Isolation

5-year warranty. See Warranty Page for details.

Slim design fits in smaller ballast compartments

Includes test switch/charge indicator accessory kit

Selectable lamp leads for optimizing light output for desired lamp type

Meets or exceeds all National Electrical Code and Life Safety Code
Emergency Lighting Requirements

International Voltage and Damp Location Models available


DIMENSIONS