| LUMEN OUTPUT |
|
(1) Lamp - 1400 lumens (2) lamps - 700 lumens per lamp |
| LAMPS OPERATED |
|
Most 2'-8' single, bipin T8 & T12, long compact and 2'-4' 14W to 54W T5 HO or VHO fluorescent lamps |
| EMERGENCY OPERATION |
|
90 Minutes |
| PRODUCT DESCRIPTION |
|
The I-320 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-320 switches to the emergency
mode and operates one or two of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can, and can be mounted in the wireway or on top of the fixture. The I-320 can be used with most 2'-8' T8 thru T12 and 2'-4' 14W to 54W T5 lamps, with an initial output of up to 1400 lumens for one or two lamps
and features lamp selector leads for optimizing light output for the designated lamp type. The I-320 delivers high performance in a slim design, and is ideal for use in fixtures where compartment space is limited.
|
|
||||
| AVERAGE LUMEN RATINGS | ||
| Lamp | 1 Lamp | 2 Lamps |
| F16 T8 | 1125 | 1100 |
| F17 T8 | 1125 | 1100 |
| F25 T8 | 1200 | 1150 |
| F28 T8 | 1215 | 1175 |
| F32 T8 | 1350 | 1350 |
| 8' T8 (FO96) (59W) | 1400 | |
| F20 T12 | 680 | |
| F39 T12 | 1000 | |
| F40 T12 | 1150 | |
| F48 T12 | 1150 | |
| 8' T12 (F96T12) (60W) | 1125 | |
| 14W T5 | 850 | |
| 21W T5 | 1150 | |
| 24W T5 | 925 | |
| 28W T5 | 1050 | |
| 39W T5 | 1100 | |
| 54W T5 | 1150 | |
| 20W Circline | 1125 | |
| 22W Circline T9 | 1000 | |
| 22W Circline T5 | 1000 | |
| 40W Circline T8 | 1125 | |
| 40W Circline T5 | 1200 | |
| 57W PL CF Quad 4 Pin | 1160 | |
| 70W PL CF Quad 4 Pin | 1200 | |
| 36W Long Compact | 1050 | |
| 40W Long Compact | 1050 | |
| 50W Long Compact | 1100 | |
| 55W Long Compact | 1100 | |
| FEATURES | |
|
U.L. and C.U.L. Listed Will cold start and operate all specified lamps Long-life high-temperature recyclable Ni-Cad battery 90-minute emergency operation Dual voltage 120/277V, 60Hz Time Delay Enhancement Open Circuit Isolation 5-year warranty. See Warranty Page for details. Slim design fits in smaller ballast compartments Includes test switch/charge indicator accessory kit Selectable lamp leads for optimizing light output for desired lamp type Meets or exceeds all National Electrical Code and Life Safety Code Emergency Lighting Requirements International Voltage and Damp Location Models available |
|
| DIMENSIONS |
|