LUMEN OUTPUT
(1) Lamp - 500 lumens
LAMPS OPERATED
Most 2'-4' T8 & T12 single and bipin fluorescent lamps
EMERGENCY OPERATION
90 Minutes

PRODUCT DESCRIPTION
The I-32 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-32 switches to the emergency mode and operates one of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can. The I-32 can be mounted in the wireway or on top of the fixture, and is UL Listed for retrofit applications. The I-32 can be used with most 2'-4' T8 thru T12 and 28W T5 lamps, with an initial output of up to 500 lumens for one lamp.



TECHNICAL SPECIFICATIONS
Input Voltage

Input Wattage

Lamps Operated


Emergency Operation

Initial Illumination

Approval

Weight

120/277V 60Hz

2.5 Watts

Most 2'-4' single, bipin
28W T5 thru T12 fluorescent lamps

90 Minutes

(1) Lamp up to 500 lumens

UL and CUL Listed

1.5 lbs



AVERAGE LUMEN RATINGS
Lamp 1 Lamp
F17 T8 450
F28 T8 460
F32 T8 475
28W T5 500
F20 T12 425
F40 T12 450
40W Long Compact 450
40W Circline 450


FEATURES
U.L. and C.U.L. Listed

Will cold start and operate all specified lamps

Long-life high-temperature recyclable Ni-Cad battery

90-minute emergency operation

Dual voltage 120/277V, 60Hz

Time Delay Enhancement

Open Circuit Isolation

5-year warranty. See Warranty Page for details.

Slim design fits in smaller ballast compartments

Includes test switch/charge indicator accessory kit

Selectable lamp leads for optimizing light output for desired lamp type

Meets or exceeds all National Electrical Code and Life Safety Code
Emergency Lighting Requirements

International Voltage Models available



DIMENSIONS





Back to IOTA Engineering Home Page