LUMEN OUTPUT
(1) Lamp - 700 lumens
LAMPS OPERATED
Most 2'-4' T8 & T12 single and bipin fluorescent lamps
EMERGENCY OPERATION
90 Minutes

PRODUCT DESCRIPTION
The I-40 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-40 switches to the emergency mode and operates one of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can. The I-40 can be mounted in the wireway or on top of the fixture, and is UL Listed for retrofit applications. The I-40 can be used with most 2'-4' lamps, with an initial output of up to 700 lumens for one lamp.



TECHNICAL SPECIFICATIONS
Input Voltage

Input Wattage

Lamps Operated

Emergency Operation

Initial Illumination

Operating Temp

Approval

Weight

120/277V 60Hz

3.5 Watts

Most 2'-4' single, bipin T8 & T12,

90 Minutes

(1) Lamp 700 lumens

0 to 55 degrees C

UL and CUL Listed

2.4 lbs



AVERAGE LUMEN RATINGS
Lamp 1 Lamp
F17 T8 450
F32 T8 700
F20 T12 390
F40 T12 660
40W Long Compact 600
20W Circline 625
40W Circline 650


FEATURES
U.L. and C.U.L. Listed

Will cold start and operate all specified lamps

Long-life high-temperature recyclable Ni-Cad battery

Galvanized steel case

90-minute emergency operation

Dual voltage 120/277V, 60Hz

Time Delay Enhancement

Open Circuit Isolation

5-year warranty. See Warranty Page for details.

Includes test switch/charge indicator accessory kit

DL model suitable for use in enclosed and gasketed fixtures

Meets or exceeds all National Electrical Code and Life Safety Code
Emergency Lighting Requirements

International Voltage and Damp Location Models available



DIMENSIONS