| LUMEN OUTPUT |
| (1) Lamp - 700 lumens |
| LAMPS OPERATED |
| Most 2'-4' T8 & T12 single and bipin fluorescent lamps |
| EMERGENCY OPERATION |
|
90 Minutes |
| PRODUCT DESCRIPTION |
|
The I-40 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-40 switches to the emergency
mode and operates one of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can. The I-40 can be mounted in the wireway or on top of the fixture, and is UL Listed for retrofit
applications. The I-40 can be used with most 2'-4' lamps, with an initial output of up to 700 lumens for one lamp.
|
|
||||
| AVERAGE LUMEN RATINGS | |
| Lamp | 1 Lamp |
| F17 T8 | 450 |
| F32 T8 | 700 |
| F20 T12 | 390 |
| F40 T12 | 660 |
| 40W Long Compact | 600 |
| 20W Circline | 625 |
| 40W Circline | 650 |
| FEATURES | |
|
U.L. and C.U.L. Listed Will cold start and operate all specified lamps Long-life high-temperature recyclable Ni-Cad battery Galvanized steel case 90-minute emergency operation Dual voltage 120/277V, 60Hz Time Delay Enhancement Open Circuit Isolation 5-year warranty. See Warranty Page for details. Includes test switch/charge indicator accessory kit DL model suitable for use in enclosed and gasketed fixtures Meets or exceeds all National Electrical Code and Life Safety Code Emergency Lighting Requirements International Voltage and Damp Location Models available |
|
| DIMENSIONS |
|