LUMEN OUTPUT
(1) Lamp - 700 lumens
(2) lamps - 350 lumens per lamp
LAMPS OPERATED
Most 2'-8' single, bipin
T8 & T12, long compact, HO or VHO fluorescent lamps
EMERGENCY OPERATION
90 Minutes

PRODUCT DESCRIPTION
The I-48 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the I-48 switches to the emergency mode and operates one or two of the existing lamps for 90 minutes. The unit contains a battery, charger, and inverter circuit in a single can. The I-48 can be mounted in the wireway or on top of the fixture, and is UL Listed for retrofit applications. The I-48 can be used with most 2'-8' lamps, with a total initial output of up to 700 lumens for one or two lamps.



TECHNICAL SPECIFICATIONS
Input Voltage

Input Wattage

Lamps Operated



Emergency Operation

Initial Illumination*



Approval

Weight

120/277V 60Hz

3.5 Watts

Most 2'-8' single, bipin
T8 & T12, long compact,
HO or VHO fluorescent lamps

90 Minutes

(1) Lamp 700 lumens
(2) lamps 350 lumens each lamp
*Long compact - (1) lamp only

UL and CUL Listed

2.4 lbs



AVERAGE LUMEN RATINGS
Lamp 1 Lamp 2 Lamps
F17 T8 450 650
F32 T8 700 675
8' T8 (FO96) (59W) 675
F20 T12 390 650
F40 T12 660 650
8' T12 (F96T12) (60W) 650
40W Long Compact 600
50W Long Compact 625
55W Long Compact 650
20W Circline 390
22W Circline T9 400
22W Circline T5 425
40W Circline T8 650
40W Circline T5 650
55W Circline T5 650


FEATURES
U.L. and C.U.L. Listed

Will cold start and operate all specified lamps

Long-life high-temperature recyclable Ni-Cad battery

Galvanized steel case

90-minute emergency operation

Dual voltage 120/277V, 60Hz

Time Delay Enhancement

Open Circuit Isolation

5-year warranty. See Warranty Page for details.

Includes test switch/charge indicator accessory kit

DL model suitable for use in enclosed and gasketed fixtures

I-48-EM-A Remote Mounting Option

Meets or exceeds all National Electrical Code and Life Safety Code
Emergency Lighting Requirements

International Voltage and Damp Location Models available



DIMENSIONS