| LUMEN OUTPUT |
|
(1) Lamp - 1300 lumens (2) lamps - 650 lumens per lamp |
| LAMPS OPERATED |
| Most 2'-8' single, bipin T8 & T12, long compact, HO or VHO, and 2'-4' 28W-54W T5 fluorescent lamps |
| EMERGENCY OPERATION |
|
90 Minutes |
| PRODUCT DESCRIPTION |
|
The ISD-80 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the ISD-80 switches to the emergency
mode and operates one or two of the existing lamps for 90 minutes. The ISD-80 will self-test for thirty seconds monthly and for ninety minutes annually and will diagnose potential problems within
the light fixture. If problems are encountered, the unit will specify failure of the battery, charge, lamp, or inverter by means of an audible beep and flashing red indicator. The dual color LED indicator is lit red when charging and lit green
when ready. The unit contains a battery, charger, and inverter circuit in a single can. The ISD-80 can be mounted in the wireway or on top of the fixture, and is UL Listed for factory installation or retrofit
applications. The ISD-80 can be used with most 2'-8' lamps, with an initial output of up to 1300 lumens for one or two lamps.
|
|
||||
| AVERAGE LUMEN RATINGS | ||
| Lamp | 1 Lamp | 2 Lamps |
| F16 T8 | 1125 | 1100 |
| F17 T8 | 1125 | 1100 |
| F25 T8 | 1200 | 1150 |
| F32 T8 | 1350 | 1350 |
| 8' T8 (FO96) (59W) | 1300 | |
| F20 T12 | 680 | |
| F40 T12 | 1150 | |
| F48 T12 | 1150 | |
| 8' T12 (F96T12) (60W) | 1125 | |
| 28W T5 | 1050 | |
| 39W T5 | 1100 | |
| 54W T5 | 1150 | |
| 20W Circline | 1125 | |
| 40W Circline | 1125 | |
| 57W PL CF Quad 4 Pin | 1160 | |
| 70W PL CF Quad 4 Pin | 1200 | |
| 36W Long Compact | 1050 | |
| 40W Long Compact | 1050 | |
| 50W Long Compact | 1100 | |
| 55W Long Compact | 1100 | |
| FEATURES | |
|
U.L. and C.U.L. Listed Long-life high-temperature recyclable Ni-Cad battery Galvanized steel case 90-minute emergency operation Automatic monthly and annual testing Internal self-diagnostic circuitry Tests lamp frequency, battery charge and discharge current Includes one-piece test switch and dual color charge indicator (LPTS) accessories Universal voltage 110-277V, 50-60Hz Time Delay Enhancement Open Circuit Isolation 5-year warranty. See Warranty Page for details. Selectable lamp leads for optimizing light output for desired lamp type DL model suitable for use in enclosed and gasketed fixtures Meets or exceeds all National Electrical Code and Life Safety Code Emergency Lighting Requirements |
|
| DIMENSIONS |
|