| DLS TROUBLESHOOTING STEPS | |
|
In situations where the battery is not charging, or you wish to confirm that the DLS is functioning properly, follow
these diagnostic procedures: 1) Check the DLS fuses near the fan. If the fuses are not blown, proceed to step #2. 2) Unplug the DLS and check the electrical box for 120VAC output. 3) With the DLS unplugged, disconnect the positive lead from the DLS. Be careful not to touch the wire to the ground. 4) Plug the DLS into the 120VAC and measure the DC output. The output voltage should be 13.6VDC. A correct voltage indicates the DLS is functioning properly. 5) If the voltage is incorrect, contact the IOTA Technical Support staff for assistance. |
|
|
|