   ILB-CP10-HE-SD Self-Diagnostic LED Emergency Driver Emergency Driver Specification Sheet in PDF format Installation Manual in PDF format Wiring Diagrams
IOTA ILB-CP10-HE Emergency Driver LED Operation
10 Watt LED load @ 10-60 Vdc Nominal*

10 Watts (Constant)

Emergency Operation
90 Minutes

Product Description

The ILB-CP10-HE-SD from IOTA is a UL Listed self-diagnostic LED emergency driver that allows the same LED fixture to be used for both normal and emergency operation. In the event of a power failure, the ILB-CP10-HE-SD switches to the emergency mode and operates the existing fixture for 90 minutes. The unit contains a battery, charger, and converter circuit in a single enclosure. The unit will operate an LED array load at 10 watts with constant power at a rated output voltage of 10V-60V. The Constant Power design of the ILB-CP10-HE-SD maintains the output wattage to the LED array even as the system voltage diminishes. The integrated self-diagnostic circuitry will automatically conduct monthly 30-second and annual 90-minute tests to verify proper emergency capability per Life Safety Code requirements. The ILB-CP10-HE-SD features high-efficiency performance and complies with CEC efficiency standards.

Product Description

Input Voltage: (Universal) 120-277Vac, 50/60 Hz

Input Rating (120V/277V): 3.7 Watts (max)

Output Voltage* 10-60 Vdc Class 2 Compliant

Output Current 1A (@10Vdc) - 0.16A (@60Vdc)

Output Power 10 Watts (constant)

Max. AC Driver Output Current 3Adc

Surge Protection Meets ANSI/IEEE C62.41.2-2002

Emergency Operation 90 minutes

Operating Temp 0 to 55 C

THD < 20%


High Temp Nickel-Cadmium
24 Hour Recharge
7-10 Year Life Expectancy


3.5 lbs (-B, -TM)
3.75 lbs (-J, -RJ)
4.0 lbs (-A, -R)


UL Listed for factory and field installation
California Energy Commission (CEC)
*Max. output voltage in emergency mode
is 58.5 Vdc with +tolerance of 1.5 volts.

  • Satisfies the periodic testing requirements in accordance with NFPA 101

  • Internal self-diagnostic circuitry tests battery, charger, and load performance

  • High Efficiency design meets CEC efficiency standards (CEC-400-2014-009-CMF)

  • UL Listed for field installation

  • Constant Power Design maintains emergency illumination through
    90-minute runtime with no light degradation

  • Two-wire universal AC input

  • Self-sensing output voltage operates various product types, reducing product SKUs for emergency options


  • UL 924 Listed for U.S. and Canada

  • UL 1310 Certified, Class 2 Compliant

  • Six mounting configurations available

  • Long life high temperature recyclable Ni-Cad battery

  • Galvanized steel case

  • Includes dual-color TBTS test switch/charge indicator

  • For use with switched and unswitched fixtures

  • Expanded functionality allows tests to be manually initiated or canceled by local switching controls

  • 5-year warranty. See Warranty Page for details.

  • Meets or exceeds all NEC, IBC, and Life Safety Code Emergency Lighting Requirements

  • Rated for use in Plenum, Damp Location, Recessed Type IC, and Enclosed and Gasketed Fixtures.

  • RoHS Compliant

  • Patented. Visit for more details.


15.37" x 2.24" x 1.3" (Mounting Center: 15.0")

LED Emergency Driver Dimensions

15" x 2.2" x 1.2" (Mounting Center: 14.64")

LED Emergency Driver Dimensions

IOTA Links

Home Page

LED Emergency Drivers

IIS Series Inverters

Fluorescent Emergency Ballasts

Product Links

Specification Sheet

Installation Manual

Wiring Diagrams

Emergency Solutions Product Guide

ILB-CP Specifier's Toolkit

Contact IOTA

IOTA Directory

Request Literature

Find Your Local IOTA Sales Representative

Technical Services Page

T: 1-800-866-4682  •  F: (520) 741-2837  •  PO Box 11846 Tucson, AZ  •  1361 E. Wieding Road Tucson, AZ 85706

© 2017 IOTA Engineering, L.L.C, Tucson AZ. All Rights Reserved.