LUMEN OUTPUT
(1) Lamp - 700 lumens
LAMPS OPERATED
Most 2'-4' T8 & T12 single and bipin fluorescent lamps
EMERGENCY OPERATION
90 Minutes

PRODUCT DESCRIPTION
The D-48-T provides emergency illumination of up to 3000 lumens and operates in conjunction with the existing lamps and ballasts in facilities that have 48V central battery systems. The D-48-T is a combination solid state 48V inverter ballast and AC sensing relay. When the AC power fails, the D-48-T automatically switches to the emergency mode, and operates one of the existing lamps at full light output for as long as the 48V battery capacity is available. Typical application for the D-48-T is telephone company operations buildings.



TECHNICAL SPECIFICATIONS
Standby Input Voltage

Standby Current Draw

Operating Input Voltage

Operating Current Draw

Lamps Operated


Initial Illumination

Approval

Weight

120/277V 60Hz

.22A

48VDC

.85A

Most 2'-5' single, bipin T8 & T12
HO or VHO fluorescent lamps

3000 lumens

UL Listed

2.5 lbs



FEATURES
U.L. Listed

Will cold start and operate all specified lamps

Full light output

Galvanized steel case

Dual voltage 120/277V, 60Hz

5-year warranty. See Warranty Page for details.

Meets or exceeds all National Electrical Code and Life Safety Code
Emergency Lighting Requirements



DIMENSIONS