LUMEN OUTPUT
(One 10W-42W Lamp) - 650 lumens
(Two 10W-18W Lamps) - 325 lumens
LAMPS OPERATED
10W-42W 4-Pin Rapid Start Compact Lamps
(Twin, Triple, Quad Tube, 2D and Straight)
and 18W-36W Long Compact Lamps
EMERGENCY OPERATION
90 Minutes AC Operation

PRODUCT DESCRIPTION
The I-42-L Compact Fluorescent Emergency Ballast Kit is designed to allow shallow or unusually-shaped fixtures (such as wall packs, sconces, and recessed stair fixtures) to be configured for normal and emergency operation. The unit consists of an open circuit board assembly and battery pack which is offered in three profile options. In the event of a power failure, the I-42-L switches to the emergency mode and operates one or two of the existing lamps for 90 minutes. The I-42-L can be used with most 10W-42W, 4-pin, quad and triple tube compact fluorescent lamps and 18W-36W long compacts, with an initial output of up to 650 lumens for one or two lamp. The I-42-L utilizes AC output to ensure compatibility with new lamp technologies, and features lamp selector leads for optimizing light output for designated lamp types. The I-42-L is a U.L. Recognized Component for factory installation only.



TECHNICAL SPECIFICATIONS
Input Voltage

Input Wattage

Lamps Operated



Emergency Operation


Initial Illumination*



UL Conditions of Acceptability



120/277V 60Hz

3.5 Watts

10W-42W 4-Pin Rapid Start Twin, Triple,
Quad, 2D and Straight Compact Lamps,
18W-36W Long Compact Lamps

(1) 10W-42W or (2) 10W-18W
90 Minutes

650 lumens
(2) Lamps 325 lumens each lamp
*Long Compact - (1) lamp only

Must be factory wired

Battery Temperature must not
exceed 61 degrees C


AVERAGE LUMEN RATINGS
Lamp 1 Lamp 2 Lamps
13W PL CF 350 400
18W PL CF QUAD 350 550
26W PL CF QUAD 425
32W PL CF QUAD 4-PIN 600
42W PL CF QUAD 4-PIN 750
F282 D/42 475 500
F382 D/42 500 650
18W Long Compact 500
24W Long Compact 575
36W Long Compact 650


FEATURES
U.L. Recognized Component

Will cold start and operate all specified lamps

Long-life high-temperature recyclable Ni-Cad battery

90-minute emergency operation

Dual voltage 120/277V, 60Hz

AC output in the emergency mode

Time Delay Enhancement

Open Circuit Isolation

5-year warranty. See Warranty Page for details.

Includes one-piece TBTS test switch and charge indicator

Selectable lamp leads for optimizing light output for desired lamp type

Meets or exceeds all National Electrical Code and Life Safety Code
Emergency Lighting Requirements

International Voltage Models available



DIMENSIONS
CIRCUIT BOARD ASSEMBLY

Length
Width
Height (includes .25 inch stand-off)
Mounting Centers
Weight

BATTERY PACK

Stick
Length
Width
Height
Weight

In-Line
Length
Width
Height
Weight

Triangle
Length
Width
Height
Weight


4 in.
2.75 in.
1.25 in.
3.5 x 2.3 in.
.5 lbs




7.375 in.
1.375 in.
1.375 in.
1 lb.


3.875 in.
1.25 in.
2.375 in.
1 lb.


2.6 in.
2.4 in.
2.375 in.
1 lb.