| LUMEN OUTPUT |
| (1) Lamp - 500 lumens |
| LAMPS OPERATED |
| Most 2'-4' T5 up to 28W or T8 linear fluorescent lamps |
| EMERGENCY OPERATION |
|
90 Minutes |
| PRODUCT DESCRIPTION |
| The ISL-28 Fluorescent Emergency Ballast allows the same fixture to be used for both normal and emergency operation. In the event of a power failure, the ISL-28 switches to the emergency mode and operates one of the existing lamps for 90 minutes. The ISL-28 delivers high performance in a slim design. This unit is ideal for use in linear lighting fixtures where ballast compartment space is limited. The unit contains a battery, charger, and inverter circuit in a single can. The ISL-28 is UL Listed for retrofit applications and can be used with most 2'-4' T5 up to 28W and T8 fluorescent lamps at an initial output of up to 500 lumens for one lamp. |
|
||||
| AVERAGE LUMEN RATINGS | |
| Lamp | 1 Lamp |
| 14W T5 | 375 |
| 21W T5 | 425 |
| 24W T5 | 500 |
| 28W T5 | 500 |
| F17 T8 | 320 |
| F25 T8 | 360 |
| F32 T8 | 425 |
| FEATURES | |
|
U.L. and C.U.L. Listed Will cold start and operate all specified lamps Long-life high-temperature recyclable Ni-Cad battery 90-minute emergency operation Dual voltage 120/277V, 60Hz Time Delay Enhancement Open Circuit Isolation 5-year warranty. See Warranty Page for details. Slim design fits in smaller ballast compartments Includes test switch/charge indicator accessory kit Selectable lamp leads for optimizing light output for desired lamp type Meets or exceeds all National Electrical Code and Life Safety Code Emergency Lighting Requirements International Voltage and Damp Location Models available |
| DIMENSIONS |
|