   ETS-STEP ALCR Device for Step Dimming Specification Sheet in PDF format Installation Manual in PDF format Wiring Diagrams
Lumen Output
Full light output

Lamps Operated
For designated LED, fluorescent, or incandescent fixtures with bi-level dimming controls connected to an auxiliary generator or inverter supply up to 3 amps continuous.

Product Description

The IOTA ETS-STEP Emergency Lighting Control Device allows the use of local switch and step dimming control on designated emergency luminaires when emergency power is provided by a generator or inverter. The ETS-STEP senses the loss of normal AC power and bypasses local step dimming settings, allowing emergency power directly to the fixture regardless of bi-level control settings. The ETS-STEP is rated for any lamp load up to 3 amps continuous power including LED loads per NEMA 410 standards. The ETS-STEP is an ideal solution for achieving increased energy savings in accordance with most energy efficiency standards by eliminating the need to operate the designated emergency fixtures 24/7 when emergency power is sourced from a generator or inverter. The additional power lead of the ETS-STEP interfaces with the driver or ballast’s step dimming control for proper emergency operation of the fixture from the designated auxiliary supply.


Product Specifications

Input Voltage: (Dual) 120/277V 60Hz

Input Current: 35 mA

Max. Switching Current
3 Amps @ 120V
3 Amps @ 277V

Circuit Protection
3A on Control Input
3A on 120/277V outputs

Dimming Compatibility


For use with step dimming applications

Emergency Operation


The ETS-STEP allows operation of any lamp type in the designated fixture for the duration of the auxiliary supply.

Initial Illumination The ETS-STEP allows operation of any lamp type in the designated load at the full output of the lamp

Operating Temp 0° to 55° C

Surge Protection Meets ANSI/IEEE C62.41.2-2002

Weight 1.0 lbs

Approval




UL 924 Listed
   PRODUCT ADVANTAGES
  • Regain local switch control of your designated emergency fixtures powered from a generator or inverter

  • Promotes energy savings by eliminating the need for always-on fixtures

  • Step-Dimming dual relay design allows the use of step dimming controls on your emergency luminaire

  • Full light output

  • Compatible with LED loads up to 3 amps continuous in accordance with NEMA 410

   FEATURES
  • Shunts local switch devices in the emergency mode allowing for full lumen output

  • Rated for LED loads up to 3 amps continuous per NEMA 410 standards

  • Galvanized steel case

  • Dual Voltage 120/277V 60Hz

  • Rated for use in plenum fixtures

  • 5-year warranty. See Warranty Page for details.

  • Meets or exceeds all NEC, IBC, and Life Safety Code Emergency Lighting Requirements

  • RoHS Compliant



Dimensions

8.0" x 1.18" x 1.15" (Mounting Center: 7.5")

ETS-STEP Emergency Control Device Dimensions




IOTA Links

Home Page

LED Emergency Drivers

IIS Series Inverters

Emergency Ballasts for Fluorescent and LED Retrofit Lamps


Product Links

Specification Sheet

Installation Manual

Wiring Diagrams

Technical Library

Contact IOTA

IOTA Directory

Request Literature

Find Your Local IOTA Sales Representative

Technical Services Page


T: 1-800-866-4682  •  F: (520) 741-2837  •  PO Box 11846 Tucson, AZ  •  1361 E. Wieding Road Tucson, AZ 85706

© 2018 IOTA Engineering, L.L.C. All Rights Reserved.   Privacy Policy   Contact Us